How SiteSense Saved a Cold Storage Facility 656,000 kWh/Year


Overview
The SiteSense monitoring platform identified performance deviations at a cold storage warehouse that indicated significant operational inefficiencies. Using a structured diagnostic process, the facility implemented targeted corrective actions that reduced electricity consumption by 656,000 kWh annually, delivering approximately $98,000 in projected annual energy savings.
Energy Challenges
Performance reviews showed the facility was falling behind expected energy performance targets. While the annual goal was 13.9% energy savings, the site had achieved only 6.6%, creating a shortfall of approximately 171,000 kWh. This gap triggered a deeper investigation into system operation and facility conditions.
Intervention: Checklist-Driven Diagnostic Process
A detailed operational checklist was issued to gather the insights necessary to begin corrective action. Analysis identified several key issues:
Condenser performance limitations: Head pressure was operating at a fixed setpoint instead of using floating condensing pressure based on ambient conditions.
Air infiltration and envelope weaknesses: Sticking doors and damaged barriers allowed warm, humid air into low-temperature spaces, increasing frost buildup and refrigeration load.
Occupancy sensors: Lighting duration was set to 10 minutes, significantly longer than standard operating practices.
Corrective Actions Implemented
- Automated condenser wet-bulb control to synchronize head pressure with outdoor conditions in real time
- Door and envelope repairs to eliminate infiltration and improve thermal performance
- Lighting optimization by reducing occupancy timer duration from 10 minutes to 90 seconds
- Ongoing system optimization, including suction pressure optimization for LT, MT, and ULT systems
- Condenser fan and pump sequencing optimization
- Autopurger restoration to improve long-term efficiency by removing non-condensable substances from the system
Results: Clear & Rapid Performance Improvement
Following implementation of the corrective actions, the facility achieved measurable improvements in energy performance. Energy savings increased by 11.4%, resulting in an estimated annual reduction of 656,000 kWh and projected annual financial savings of approximately $98,000.
- 656,000 kWh annual energy reduction
- 11.4% increase in energy savings performance
- $98,000 projected annual electricity cost savings
- Improved system efficiency through operational and control optimization
- Ongoing monitoring and optimization enabled through the SiteSense platform

Key Takeaway
By combining continuous monitoring, digital diagnostics, and targeted operational improvements, the facility transformed underperforming refrigeration operations into a high-efficiency system that delivers substantial and sustainable energy savings.